How can we help you today?

How to connect temperature sensors to TMC4TI2 cartridge ?

You can find in attachment 4 wiring examples with 3 wires RTDs, 4 wires RTDs and thermocouples.

Schneider Electric USA

Attachment(s)
TMC4TI2 tc rtd.png [35.55 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings