How can we help you today?

PM5000 Series Default IP Address, User Account Login Credentials, and Administrative Login for Webpages and Password Reset

Issue

Default IP address and login credentials to the webpage and FTP server for PM5000 series meters, and steps to reset administrative password if lost.

Product Line

PM5000 Series

Environment

Web server and meter front panel.

Resolution

Default Network Settings

IP Address: 169.254.0.10
Subnet Mask: 255.255.0.0

Explanation

The PM5000 series meters have different default login credentials depending on the firmware version and meter model.

Legacy firmware refers to older versions (v2.9.9 and earlier for most models).
New firmware refers to versions v4.0.0 and above (or equivalent for other models).
Use the table below to identify which credentials apply to your meter.

How to Check Firmware Version

On the meter display:
Navigate to Maint > Diag > Info to view the firmware version.

Default Login Credentials by Firmware Version

Meter Models

Firmware Type & Models

Username

Password

Notes

Legacy (≤ v2.9.9 / v3.2.9)
Models: PM5560 / PM5562 / PM5563 / PM5580 (v2.9.9 and earlier), PM5570 / PM5660 / PM5760 (v3.2.9 and earlier), PM5650 (v2.12.9 and earlier), PM5561 (v10.9.9 and earlier), PM5661 / PM5761 (v11.2.9 and earlier)

user1

pass1

Web Master account

Legacy (≤ v2.9.9 / v3.2.9)
Models: Same as above

user2

pass2

Product Master account

Legacy (≤ v2.9.9 / v3.2.9)
Models: Same as above

0000

Display passcode

New (≥ v4.0.0 / v6.0.0)
Models: PM5560 / PM5562 / PM5563 / PM5580 (v4.0.0 and above), PM5570 / PM5660 / PM5760 (v6.0.0 and above), PM5650 (v4.10.0 and above), PM5561 (v12.0.0 and above), PM5661 / PM5761 (v14.0.0 and above)

Administrator

MAC address (uppercase, no colons)

Example: 00:80:f4:02:14:38 → 0080F4021438; Mandatory password change

New (≥ v4.0.0 / v6.0.0)
Models: Same as above

Guest

Powerlogic@1

Recommended to change immediately

Password Policy

Minimum length: 8–16 characters.
Must include:
- At least 1 uppercase letter
- At least 1 number
- At least 1 special character
Session timeout: 10 minutes.
Lockout after 5 failed attempts (2-minute lock).
HTTPS enabled by default for new firmware.
FTP disabled by default (can enable via display or webpages).

Password Reset (if lost)

1. Go to the meter front panel.
2. Navigate to Maint > Reset > User Acc Resets.
3. Enter passcode (default: 0).
4. Confirm reset.
Note: This deletes all customizations and data.

References:

Schneider Electric USA

Attachment(s)
PowerLogic™ PM5500-PM5600-PM5700 series HRB1684301-16 User Manual.pdf [6.5 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings