What does a stop (shown as st0p) message indicate on an H, J, or L frame trip unit?
Product Line:
Powerpact H, J, L Circuit Breakers with Micrologic trip units
Resolution:
The stop message may indicate one of three things.
- It may indicate that the trip unit is set up for a neutral CT but none is connected. If this is the case, it will clear by pressing OK twice when the NCT is installed or a jumper is placed between T1 and T2. If NCT is not installed, pressing OK will momentarily clear the STOP error, but it will come right back.
- It may indicate a bad NCT; if one is installed and getting the STOP error, remove the neutral CT and place a jumper across T1 and T2 and press the OK button twice and see if the error clears
- It may indicate a BSCM failure.
- It may indicate an error with the trip unit. It is possible the trip unit connection was interrupted while the breaker was in operation and this error can be easily reset by unlocking the trip unit screen and pressing the OK button to acknowledge the error.
- Also try power cycling the trip unit
- If none of the above clear the error, the trip unit is damaged and the trip unit or breaker will need to be replaced.
Instruction Manual 48940-312-01