How can we help you today?

What is the part number for the replacement handle used for a Nema 3R Speed D Switchboard?

Issue:
Is there a replacement handle for a Nema 3R Speed D Switchboard?

Product Line:
Speed D SWBD

Environment:
Maintenance

Cause:
Replacement

Resolution:
The replacement handle for ALL Speedy D Switchboards is 50552-108-01

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.