What is the voltage threshold for shunt trips for circuit breakers?

Issue:
Shunt trip voltage thresholds

Product Line:
Circuit Breakers

Resolution:
The 120 Vac shunt trip threshold is 55% of the rated voltage.
For all other shunt trips for legacy breakers (F, K, L, M, N, and P frames), the threshold is 75% of the rated voltage.
For Powerpact and Masterpact breakers, the threshold is 70% of rated voltage.