Do the Powerpact H, J, and L breakers work with the AMS and/or ERMS arc fault reduction system?
Issue:
ERMS Arc Fault reduction with Powerpact H, J, L breakers
Product Line:
Circuit Breakers
Resolution:
AMS system:
ERMS Arc Fault reduction with Powerpact H, J, L breakers
Product Line:
Circuit Breakers
Resolution:
AMS system:
- Powerpact L breakers with 6.3A, 6.3E, 5.3A, or 5.3E trip units will function with the AMS system. Powerpact H and J breakers will not because they cannot accept a ZSI restraint signal.
- H, J, and L breakers will NOT work with the ERMS arc flash reduction system.
Released for: Schneider Electric USA