Editing a Reporter/ RepGen report causes Reporter to "lockup" or freeze when OK is clicked.

Issue
Changes are made to an existing report in RepGen edit mode and OK is clicked, the software either freezes and shows not responding or crashes and disappears.

Product Line
ION Enterprise
Struxureware Power Monitoring
Power Monitoring Expert

Environment
Any ION software where the excel based RepGen is used for reporting.

Cause
There is a pre-defined Named Range of cells in the report that tells the macros where to look for the names of the datasheets to process - appropriately named "Datasheets".

When a report is edited, and OK is clicked, the program actually deletes several empty rows from the report.
This is more prevalent in large systems as the number of devices in a single report causes the named range blank region to shrink more quickly each time the report is edited.

When the Named Range becomes smaller than the number of queries added to the report,
the remaining datasheets in the report are deleted and disregarded.
This causes the save of the report edits to become "lost" and unable to fully save, resulting in the locked state.

Resolution
1.) Open the appropriate report template in Excel.
Select the report in RepGen and click Preview.
-or-  Find the report in the ION install directory ...config\reports
2.)  Expand the 'Datasheets' Named Range to include more rows.
Excel 2003:
- unhide sheet |PRIVATE|Datasheets
Format -> Sheet -> Unhide
Select |PRIVATE|Datasheets
- Expand the Named Range
Insert -> Name -> Define...
- Select 'Datasheets' name.
- in 'Refers to:' field, change it to include more rows - $A3:$A606 increase to A$65000 (for example)

Excel 2007, 2010, 2013:
- Expand the Named Range
Formulas tab -> Name Manger
- Select Datasheets in the Name Manager Window
- in 'Refers to:' field, change it to include more rows - $A3:$A606 increase to A$65000 (for example)
- click Close and it will ask you to save select Yes
3.) Save the Excel document (file type should remain xls)

The report can now be edited without issue.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.