Where can I find the proper bolt sizes for the Seismic qualifications for panelboards?
Issue:
Where can I find the proper bolt sizes for the Seismic qualifications for panelboards?

Product Line:
Panelboards

Environment:
Circuit breaker panelboards sold and supported in the USA.

Cause:
Seismic qualifications required

Resolution:
Please refer to the attached Seismic Instruction Label.
All I-Line, NF, NF Column-Width, NQ, NQ Column-Width, NQOB Column-Width, NQOD and
QMB panelboards are seismic qualified when their Type 1 enclosures are mounted at the
locations shown below and use the indicated number of grade 5 steel bolts. NQ and NQOD
panels must also be equipped with bolt-on breakers.

When a side extension is used, all mounting hole locations in the side extension must be used. N represents total number of bolts used for the panel and the side extension.

To be seismic qualified, Type 3R, 3S, 5 and 12 enclosures must be mounted with grade 5 steel bolts and comply with the mounting instructions shipped with the enclosures. Also, NQ and NQOD panels must be equipped with bolt-on type breakers.

Schneider Electric USA

Attachment(s)
SeismicInstructionLabel.pdf [121.34 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Tech Support: 877-342-5173
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings