Video: How is the automatic restart function enabled on Altivar Process drives?
Resolution:
To activate this feature, follow these steps on the drive:
-
Set the control mode
- Go to: Complete Settings → Command and Reference
- Set 2 wire type to Level Control
-
Enable automatic restart
- Go to: Complete Settings → Error/Warning Handling
- Set Auto Fault Reset to Yes
-
Retry duration
- The drive will attempt to reset the fault during the time defined in Fault Reset Time
- Default value: 5 minutes
For automatic restart to work properly, all of the following must be met:
- The drive must be configured in 2-wire control mode
- A run command (RUN) must be active
- The fault must be resettable automatically
- The cause of the fault must be resolved
Note: This function does not work if the drive is controlled via the HMI or serial communication.
Enable Catch on the Fly (under Error/Warning Handling) so the drive can synchronize with the motor if it is already spinning when the restart occurs.
The lists of fault codes that can be cleared automatically are listed in the ATV600 Programming Manual and ATV900 Programming Manual.
Si este artículo no responde a tu pregunta, consulta nuestra base de datos de preguntas frecuentes, donde encontrarás respuestas a las preguntas más comunes:
Preguntas Frecuentes - Schneider Electric (se.com)
Si la sección de preguntas frecuentes no resolvió tu problema, puedes llamarnos al 55 5804 5000 Opción 1, Opción 2 o enviarnos un correo electrónico a customercare.mx@se.com para crear un caso con nuestro equipo de Soporte Técnico.
Si no te encuentras en México o Centroamérica, por favor contacta a tu Centro de Atención al Cliente local para recibir asistencia:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric USA
Attachment(s)
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.