What is the standard amps per square inch on panelboard bussing?
Issue:
How is the standard amps on panelboard bussing rated, per square inch , temperature?
Product Line:
Circuit breaker panelboards sold and supported in the USA.
Environment:
Application
Cause:
Specification
Resolution:
Manufacturers have a choice of testing their panels by amps per sq. inch or heat rise.
Schneider chooses to test by the heat rise method as we feel it is a better test of how connections and joints will react based on actual temperatures rather than the sq. in. calculation method.
We don't have an amps per sq. in. rating for our panels. If per square in rating is needed, it would require the selection to High Density Buss option of 750 amps per sq. in. for Aluminum, or 1000 amps per sq. in. for Copper in product selectors.
How is the standard amps on panelboard bussing rated, per square inch , temperature?
Product Line:
Circuit breaker panelboards sold and supported in the USA.
Environment:
Application
Cause:
Specification
Resolution:
Manufacturers have a choice of testing their panels by amps per sq. inch or heat rise.
Schneider chooses to test by the heat rise method as we feel it is a better test of how connections and joints will react based on actual temperatures rather than the sq. in. calculation method.
We don't have an amps per sq. in. rating for our panels. If per square in rating is needed, it would require the selection to High Density Buss option of 750 amps per sq. in. for Aluminum, or 1000 amps per sq. in. for Copper in product selectors.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.