Issue
There is a need to query the database to extract data using Vista.
Product Line
Power Monitoring Expert (any version)
Environment
Vista
Cause
A database snapshot was taken.
NOTE: The procedure on how to create a database snapshot is explained in article FA282751.
Resolution
2. Create a new Data Log Viewer and configure it as follows:
3. Data can be seen up to the time the snapshot was taken:
There is a need to query the database to extract data using Vista.
Product Line
Power Monitoring Expert (any version)
Environment
Vista
Cause
A database snapshot was taken.
NOTE: The procedure on how to create a database snapshot is explained in article FA282751.
Resolution
The procedure to connect to a snapshot is the same as connecting to an archive and explained below:
1. In Designer > QueryServer create a new query module and configure it as shown below. It is assumed the name of the snapshot is ION_Data_Snap:
1. In Designer > QueryServer create a new query module and configure it as shown below. It is assumed the name of the snapshot is ION_Data_Snap:
2. Create a new Data Log Viewer and configure it as follows:
3. Data can be seen up to the time the snapshot was taken: