Video: How to Wire a Square D™ 9013 Power Pressure Switch

Issue:
Identify how to wire a 9013 pressure switch

Product Line:
Square D™ 9013 Power Pressure Switches

Environment:
Products sold in the US

Resolution:
When looking directly at the switch you should see four terminals going from left to right. You want your power going to the outside terminals of the device. The two inside terminals should be wired to your pump/motor.

When done it should be both black wires on one side, and both red/white on the other.