How can we help you today?

What licenses are required for PowerSCADA Anywhere in PSO 8.1 and above?

Issue
User wants to confirm what licensing is required to implement PowerSCADA Anywhere

Product
PowerSCADA Operation 8.1
PowerSCADA Operation 8.2
PowerSCADA Operation 9.0

Environment
PowerSCADA Operation Remote Client

Cause
Documentation includes some data or conflicting data regarding what licensing is required for PowerSCADA Anywhere

Resolution
In order to implement PowerSCADA Anywhere, 3 separate license components are needed
1) PowerSCADA Anywhere Client License (5 seats per license)
2) PowerSCADA Operation client license, 1 per desired seat (either control or view-only)
3) Microsoft Client Access License, 1 per desired seat

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings