Issue:
Is it required for Medium voltage Switchgear to have visible switch blades?
Product Line:
Medium voltage Switchgear
Environment:
Products sold and used in the United States
Resolution:
The code requires a visible disconnect for medium voltage switchgear. In withdrawable switchgear, this is accomplished by removing the breaker from the connected position. In fixed mounted switchgear, the visible isolation is accomplished via the use of a disconnect switch.
Is it required for Medium voltage Switchgear to have visible switch blades?
Product Line:
Medium voltage Switchgear
Environment:
Products sold and used in the United States
Resolution:
The code requires a visible disconnect for medium voltage switchgear. In withdrawable switchgear, this is accomplished by removing the breaker from the connected position. In fixed mounted switchgear, the visible isolation is accomplished via the use of a disconnect switch.
Released for: Schneider Electric USA



