What Is the Trip (Fault) Status of Terminals 15 and 16 on an S-Flex Drive?
Resolution:
On an S-Flex (ATV212-based) drive, terminals 15 (FLC) and 16 (FLB) form a normally closed relay contact when configured for Trip operation.
- During normal operation (no fault, power applied):
The contact opens. - When a fault (trip) occurs:
The contact closes. - When drive power is removed:
The contact also closes.
This behavior allows the relay to signal a fault condition or loss of power to external control or monitoring circuits.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)