Why does the S-Flex (ATV212) ramp to 60 Hz instead of following the analog input?
Resolution:
If your S-Flex (ATV212) drive is ramping the motor to 60 Hz instead of tracking the analog input signal, check the following settings:
-
Verify the input mode (FMOd):
Ensure the correct control source is selected:1= VIA (Analog Input A)2= VIB (Analog Input B)3= HMI (Keypad)4= Serial Communication
-
Check for active preset speed commands:
Review parameters F108, F110, F111, F112, F113, and F118.
If any preset speed is enabled through digital inputs, it may override the analog input. -
Confirm PID control setting (F360):
- Set F360 = 0 if PID control is not being used.
- If PID is active, the drive will follow the PID loop instead of the analog input.
-
If PID is enabled:
Verify the feedback signal and setpoint are correctly configured.
Incorrect PID setup can cause the drive to ignore the analog reference and run at a fixed speed.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance: