Will the LA main breaker accept a shunt trip in the NQMB4LA kit?
Issue:
Will the LAL36400MB with shunt trip work with the NQMB4LA kit?
Product Line:
NQ Panelboard
Environment:
Products sold in North America
Resolution:
Yes the NQMB4LA will accept the LA11021 field installed shunt trip with the LAL36400MB. The shunt trip is mounted internally so does not affect physical operation of the breaker.
Will the LAL36400MB with shunt trip work with the NQMB4LA kit?
Product Line:
NQ Panelboard
Environment:
Products sold in North America
Resolution:
Yes the NQMB4LA will accept the LA11021 field installed shunt trip with the LAL36400MB. The shunt trip is mounted internally so does not affect physical operation of the breaker.
Released for: Schneider Electric USA