How can we help you today?

Cannot download to new or replacement HMIGTO. "Incompatible version of Runtime" error appears

Article available in these languages:

  • Spanish

Issue:
Unable to download to a HMIGTO HMI. Error is "Incompatible version of Runtime".

Product Line:
HMI, Magelis

Cause:
You may have a HMI unit that is no longer supported by your version of Vijeo Designer.  This occurred when Schneider Electric increased the DRAM memory of the HMIGTO to support Vijeo XD.  The chips were upgraded to 256 MB (128 MB usable for Vijeo Designer).

Resolution:
Check the date of manufacturing sticker on the HMI unit.  If it starts with 16 or greater, then this is the newer design with increased memory.
Check your version of Vijeo Designer.  It needs to be version V6.2 SP4.1 or higher.
If you have an older version of Vijeo Designer you must update it.
Schneider Electric's software download center can be accessed at https://www.se.com/us/en/download/

NOTE: If your issue persists, please reach out to us at Technical Support:
https://www.se.com/us/en/work/support/customer-care/brand-selection/

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings