How can we help you today?

Can I Read the RJ45 Port Status on an Altivar Process PROFINET Card?

Resolution:
No. With PROFINET version 1.6, the status of the communication card's RJ45 Port A and Port B is not available through Modbus addresses or PNU parameters.

If you need to determine whether a port is connected (up) or disconnected (down), this information cannot be accessed through standard drive registers.

To monitor RJ‑45 port status, use the LLDP (Link Layer Discovery Protocol) service, which provides network link information for the PROFINET card.

Check attached file for further information.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Attachment(s)
Profinet_PortStatus.pdf [220.79 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings