How can we help you today?

Video: How do I customize short message e-mail alarm actions in Data Center Expert?

Issue:
Customizing short message e-mail alarm actions in StruxureWare Data Center Expert

Product Line:
StruxureWare Data Center Expert (DCE)

Environment:
StruxureWare Data Center Expert (DCE)

Cause:
E-mail notifications from DCE come in a pre-defined format that can not be edited.  To customize e-mail notifications, short message e-mail alert actions need to be used.

Resolution:



1) Open the DCE Client and go to: Alarm Configuration menu > Manage Alarm Actions.

2) Click on Create and then select Short Message E-Mail.  Select Next.

3) Provide an Action Name and add in the e-mail addresses that this alarm action will be sent to.

4) The subject and message fields can be customized using a defined list of macros, which are available on

https://community.se.com/t5/Manage-Alarm-Actions/Alarm-macros-for-SMS-email-alarm-action-settings-on-the-DCE/ta-p/461096

NOTE: You can use spaces, text, and return lines to organize the data that will be sent in the e-mail.

5) Associate your new alarm action to a notification policy, for instructions see Data Center Expert | Video: How do I configure StruxureWare to send e-mail notifications?

Schneider Electric USA

Explore more
Range:
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings