How can we help you today?

Video: How to change the date and time on a SEPAM 40 series relay using SFT2841.

Issue:
Need to change the date and time on the SEPAM 40 relays using SFT2841 software

Product Line:
SEPAM 40 series Relays

Environment:
SFT2841 Software

Resolution:



Step 1. Connect to the SEPAM 40 relay with SFT2841 Software,

Image

Step 2. Click on the Wrench Icon label SEPAM Diagnosis
Select The Diagnosis tab. Click on the square with 3 dots next to the date and time as shown below.

Image

Step 3. Change the Date and Time as shown below and press Apply
It will ask for a password and the default password is 0000 then press OK

Image

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings