How can we help you today?
What are the pick-up times for VIP300 relay?
For VIP300, pick-up time was not specifically mentioned in the manual, unlike with the VIP400 manual. But, there is a clause in the VIP300 manual that says:
The accuracy is indicated for a fault (sinusoidal current) that occurs when the VIP300 is already supplied by the current flowing through the circuit breaker. In the event of closing on a fault, the tripping time may be increased by:
+30 ms at 1.5 Is
+20 ms from 2 Is to 10 Is
+10 ms above 10 Is
Basically, these additional milliseconds are the time needed by the VIP300 to start reading or operating again after power cut-off.
The accuracy is indicated for a fault (sinusoidal current) that occurs when the VIP300 is already supplied by the current flowing through the circuit breaker. In the event of closing on a fault, the tripping time may be increased by:
+30 ms at 1.5 Is
+20 ms from 2 Is to 10 Is
+10 ms above 10 Is
Basically, these additional milliseconds are the time needed by the VIP300 to start reading or operating again after power cut-off.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.