How can we help you today?
What method of ground fault testing is recommended for circuit breakers?
Issue:
Ground fault testing of circuit breakers
Product Line:
Circuit Breakers
Resolution:
Schneider Electric recommends primary injection testing to comply with the requirements of NEC 230.95(C) for ground fault testing upon installation. Secondary injection testing may be done at the option of the customer for scheduled maintenance after the installation has been tested and commissioned.
For test procedures, please consult the Field Test and Maintenance Guide.
Ground fault testing of circuit breakers
Product Line:
Circuit Breakers
Resolution:
Schneider Electric recommends primary injection testing to comply with the requirements of NEC 230.95(C) for ground fault testing upon installation. Secondary injection testing may be done at the option of the customer for scheduled maintenance after the installation has been tested and commissioned.
For test procedures, please consult the Field Test and Maintenance Guide.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.