How to troubleshoot a closed breaker that has voltage on the line side but low or no voltage on the load side
Issue:
A breaker shows no continuity when tested with an ohmmeter.
Product Line:
MCCB's
Resolution:
All contacts have a minimum voltage and current required before they will conduct. Usually this number is low enough so there is no problem with reading open circuit voltage on an energized breaker with no load, but on rare occasions, the open circuit voltage on the load side will be reduced or prevented by resistive films on the contacts. This film comes mostly from oxidation, but could contain other contaminants as well.
When this is the case, the solution is to put some load on the breaker, as then the current flow driven by line voltage will burn through the resistive film and the breaker will conduct and act normally from then on. The amount of load required depends on the amount of resistance, but a low to moderate load should be enough. It may also be helpful to toggle the breaker, as doing so will reseat the contacts and help break through the resistance.
If there is still no continuity, the breaker may be bad.
A breaker shows no continuity when tested with an ohmmeter.
Product Line:
MCCB's
Resolution:
All contacts have a minimum voltage and current required before they will conduct. Usually this number is low enough so there is no problem with reading open circuit voltage on an energized breaker with no load, but on rare occasions, the open circuit voltage on the load side will be reduced or prevented by resistive films on the contacts. This film comes mostly from oxidation, but could contain other contaminants as well.
When this is the case, the solution is to put some load on the breaker, as then the current flow driven by line voltage will burn through the resistive film and the breaker will conduct and act normally from then on. The amount of load required depends on the amount of resistance, but a low to moderate load should be enough. It may also be helpful to toggle the breaker, as doing so will reseat the contacts and help break through the resistance.
If there is still no continuity, the breaker may be bad.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.