Video: Power Monitoring Expert (PME) Disabling the Alarm Annunciator
Issue
User would like to disable the Alarm Annunciator from the web banner in EcoStruxure™ Power Monitoring Expert (PME)
Product
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Environment
Web Applications
Resolution
PME 9.0 and Greater
1) In a web browser, navigate to the Web Applications by typing in http://[server name or IP address]/web into the address bar
2) Navigate to the Settings tab
3) Click on Alarms -> Alarm Views
4) The annunciator can be entirely disabled by setting underneath the "Annunciator" section to disabled or by deselecting alarms based on priority in the "Priority Classification" tab as shown below
5) Press Save

PME 8.0
1) In Internet Explorer, navigate to the Web Applications by typing in http://[server name or Ip address]/web into the address bar
2) Navigate to the Alarms application tab
3) Click on "Settings"

4) Navigate to the Alarms tab and uncheck the "Show the Alarm Annunciator". Press OK

5) Close then reopen Internet Explorer to verify the changes took effect
PME 8.1 and PME 8.2
1) In Internet Explorer, navigate to the Web Applications by typing in http://[server name or Ip address]/web into the address bar
2) Navigate to the Alarms application tab
3) In the top right corner of the Alarms application, click on "Edit Settings"

4) Uncheck "Show the Alarm Annunciator" and press OK

5) Close then reopen Internet Explorer to verify the changes took effect
Here is a video with instructions on how to disable the Alarm Annunciator in PME 8.2:
If you would like to deactivate alarms please see: https://www.se.com/us/en/faqs/FA313760/ ,
User would like to disable the Alarm Annunciator from the web banner in EcoStruxure™ Power Monitoring Expert (PME)
Product
Power Monitoring Expert 8.x
Power Monitoring Expert 9.x
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Environment
Web Applications
Resolution
PME 9.0 and Greater
1) In a web browser, navigate to the Web Applications by typing in http://[server name or IP address]/web into the address bar
2) Navigate to the Settings tab
3) Click on Alarms -> Alarm Views
4) The annunciator can be entirely disabled by setting underneath the "Annunciator" section to disabled or by deselecting alarms based on priority in the "Priority Classification" tab as shown below
5) Press Save
PME 8.0
1) In Internet Explorer, navigate to the Web Applications by typing in http://[server name or Ip address]/web into the address bar
2) Navigate to the Alarms application tab
3) Click on "Settings"
4) Navigate to the Alarms tab and uncheck the "Show the Alarm Annunciator". Press OK
5) Close then reopen Internet Explorer to verify the changes took effect
PME 8.1 and PME 8.2
1) In Internet Explorer, navigate to the Web Applications by typing in http://[server name or Ip address]/web into the address bar
2) Navigate to the Alarms application tab
3) In the top right corner of the Alarms application, click on "Edit Settings"
4) Uncheck "Show the Alarm Annunciator" and press OK
5) Close then reopen Internet Explorer to verify the changes took effect
Here is a video with instructions on how to disable the Alarm Annunciator in PME 8.2:
If you would like to deactivate alarms please see: https://www.se.com/us/en/faqs/FA313760/ ,
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.