How can we help you today?

How to determine the firmware version for Micrologic A, P and H trip units

Issue:
What is the firmware version for

  • Micrologic 3.0A, 5.0A and 6.0A trip units
  • Micrologic 5.0P and 6.0P trip units
  • Micrologic 5.0H and 6.0H trip units


Product Line:
Circuit Breakers

Resolution:
Micrologic A Trip Units (3.0A, 5.0A, 6.0A)
The Micrologic A trip units do not have a means to access the firmware version in the field. Since January 2010, they have been using firmware version V01.029.

Micrologic P and H Trip Units (5.0P, 6.0P, 5.0H, 6.0H)
The Micrologic P and H trip units have a means to access the firmware version in the field.
The trip unit screen must have a display (must be powered).
1. On the screen on front of the P and H trip unit, press the "wrench" button
2. Scroll down to "Micrologic setup", and press enter
3. Scroll down to "Breaker selection", and press enter
4. At the very bottom of the P or H trip unit screen is the firmware version (example: PLogic-2014AN)

Note: The firmware version of Micrologic  A/P/H trip units cannot be updated.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.