How can we help you today?

What is the procedure for resetting the surge counter on Surgelogic OEM, EMA, EBA, and IMA series SPDs?

Issue:
If the surge count is elevated and there is a need to monitor the frequency of surge events or assess the remaining operational life of the Surgelogic SPD, consider implementing ongoing surge event tracking and evaluating the device’s condition based on cumulative surge exposure.

Product Line:
Surge Protection Devices

Environment:
Maintenance

Cause:
The surge counter has a high surge count and customer wants to reset counter to 0.

Resolution:
To reset the surge counter, first de-energize the unit by disconnecting all power sources. Locate the small white reset switch positioned on the underside of the diagnostic circuit board, near the diagnostic display connectors. Press and hold the switch for approximately 3 seconds. Upon release, the surge counter will reset to zero.
Rear of Diagnostic Display.

Schneider Electric USA

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.