How can we help you today?

How to troubleshoot an SCF3 fault on an Altivar Process Drive?

Article available in these languages:

  • Czech
  • , Greek
  • , Spanish
  • , Hungarian

Issue:
Troubleshooting an SCF3 fault on an Altivar Process Drive.

Resolution:

  1. Perform a diagnostic test

    • Run an IGBT/transistor test on the drive.
  2. Check the motor and motor cables

    • Inspect the cables between the drive and motor for damage or short circuits.
    • Check the motor and cable insulation.
    • Perform an insulation resistance test on the motor and cables using a megohmmeter (Megger), following the appropriate safety procedures and equipment specifications.
    • Verify that the drive and motor are properly grounded.
  3. Check the motor cable length

    • Verify the distance between the drive and motor.
    • For cable lengths over 165 ft (approximately 50 m), a load reactor or output filter may be required.
  4. Check the switching frequency

    • Review the drive's switching frequency setting.
    • Reduce the switching frequency if the application allows it.

Safety note: Disconnect power and follow the applicable lockout/tagout procedures before inspecting the drive, motor, or wiring. Do not perform an insulation resistance test through the drive.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings