What is the method for testing and rating SQ D Transformers for dB sound levels ?
Issue:
What is the method for testing and rating SQ D Transformers for dB sound levels ?
Product Line:
EX transformers
Environment:
Application
Cause:
Installation location
Resolution:
SQ D /SE determines sound levels following rigorous NEMA ST-20 methods and per that Standard:
Sound levels are measured in a laboratory setting where the ambient is 10 dB below rated and no acoustically reflecting surfaces are within 10 feet of the transformer.
Measurements are made all around the unit (including the top) at a distance of 1 foot and averaged.
The adjusted room ambient sound level is factored into the final sound level value.
What is the method for testing and rating SQ D Transformers for dB sound levels ?
Product Line:
EX transformers
Environment:
Application
Cause:
Installation location
Resolution:
SQ D /SE determines sound levels following rigorous NEMA ST-20 methods and per that Standard:
Sound levels are measured in a laboratory setting where the ambient is 10 dB below rated and no acoustically reflecting surfaces are within 10 feet of the transformer.
Measurements are made all around the unit (including the top) at a distance of 1 foot and averaged.
The adjusted room ambient sound level is factored into the final sound level value.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.