How can we help you today?

How to show a record for each alarm state change in Vijeo Designer?

Issue:
Looking for a way for the HMI to record a separate entry in the Alarm Summary whenever the alarm transitions from Active, ACK'd, and return to normal.

Product Line:
Vijeo Designer (all versions)

Resolution:
In Vijeo Designer, it is possible to show a separate record in the Alarm Summary for each state change of an Alarm Variable. To do so, simply set the property "Alarm & Events List" to Log.

By default, this property is set to "Active". In this mode, the Alarm Summary will only show alarms that are still Active. When the states change from Active to RTN, the record disappears.

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings