What are the Forms to add a TeSys T to a starter?

Issue:
What are the forms to add a TeSys T to a starter? And which TeSys T module is used?

Product Line:
NEMA Type S Starters

Environment:
North American Market

Cause:
Product Selection

Resolution:

The forms, and devices, used are dependent upon NEMA size, full load amperage, and control voltage. Please see the table below for the forms and part numbers.
NEMA SizeRangeCommunication ProtocolFormTeSys T Part Number
Control VoltageControl Voltage
100-240VAC24VDC100-240VAC24VDC
1
.4-8ModbusH612H712LTMR08MFMLTMR08MBD
ProfiBusH613H713LTMR08PFMLTMR08PBD
CANopenH614H714LTMR08CFMLTMR08CBD
DeviceNetH615H715LTMR08DFMLTMR08DBD
Ethernet TCP/IPH616H716LTMR08EFMLTMR08EBD
1.35-27ModbusH622H722LTMR27MFMLTMR28MBD
ProfiBUSH623H723LTMR27PFMLTMR08PBD
CANopenH624H724LTMR27CFMLTMR27CBD
DeviceNetH625H725LTMR27DFMLTMR27DBD
Ethernet TCP/IPH626H726LTMR27EFMLTMR27EBD
2, 35.0-100ModbusH632H732 LTMR100MFM LTMR100MBD
ProfiBusH633H733LTMR100PFMLTMR100PBD
CANopenH634H734LTMR100CFMLTMR100CBD
DeviceNetH635H735LTMR100DFMLTMR100DBD
Ethernet TCP/IPH636H736LTMR100EFMLTMR100EBD
48-160 (CT 300:5 3 turns)ModbusH652H752LTMR08MFMLTMR08MBD
ProfiBusH653H753LTMR08PFMLTMR08PBD
CANopenH654H754LTMR08CFMLTMR08CBD
DeviceNetH655H755LTMR08DFMLTMR08DBD
Ethernet TCP/IPH656H756LTMR08EFMLTMR08EBD
524-480 (CT 300:5 1 turn)ModbusH662H762LTMR08MFMLTMR08MBD
ProfiBusH663H763LTMR08PFMLTMR08PBD
CANopenH664H764LTMR08CFMLTMR08CBD
DeviceNetH665H765LTMR08DFMLTMR08DBD
Ethernet TCP/IPH666H766LTMR08EFMLTMR08EBD
648-960 (CT 600:5 1 turn)*ModbusH672H772LTMR08MFMLTMR08MBD
ProfiBusH673H773LTMR08PFMLTMR08PBD
CANopenH674H774LTMR08CFMLTMR08CBD
DeviceNetH675H775LTMR08DFMLTMR08DBD
Ethernet TCP/IPH676H776LTMR08EFMLTMR08EBD


* NEMA size 6 contactors are only rated up to 810 amps (and should not be used for greater than 810 amps), as such when the contactor rating is programmed in to the TeSys T as 810 amps the device will not let you set a full load amperage over 810 amps.

Note: To order a NEMA starter with a TeSys T motor management controller the product selector should be used.

Schneider Electric USA

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Find support resources for all your needs, in one place.