Why can’t the digital input assignments be changed on ATV630 or ATV930 drives?

Resolution:

On ATV630 and ATV930 drives, the digital input assignments shown in the Input/Output menu are read-only. This means they cannot be modified directly from that menu.

To assign a function to a digital input, you must configure it from the function’s parameter, not from the DI list.

✅ Example: Assign Reverse to DI2

  1. Go to: Complete Settings → Command and Reference
  2. Find the parameter “Reverse Assign”
  3. Set it to DI2

This method applies to all digital input assignments:

  • Select the desired function
  • Assign the corresponding digital input from within that function

Please check the following manuals:

ATV600 Programming Manual
ATV900 Programming Manual

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings