ATV61 and ATV71 basic integrated modbus setup assistance?

Issue:
Need ATV61 and ATV71 basic integrated modbus setup assistance.

Resolution:

On the drive, go to:

Menu 1.9 [COMMUNICATION] > [MODBUS NETWORK]

Configure the following parameters:

  • Add – Modbus Address: Set the drive address from 1 to 247.
  • tbr – Modbus Baud Rate: Select 4.8, 9.6, 19.2, or 38.4 kbaud.
  • tFO – Modbus Format: Select 8O1, 8E1, 8N1, or 8N2, as required by the Modbus network.
  • ttO – Modbus Timeout: Set the timeout from 0.1 to 30 seconds.

After changing any Modbus communication settings, power cycle the drive. Wait until the drive display turns off completely before restoring power.

RJ45 Modbus wiring:

  • Pin 4: Data +
  • Pin 5: Data -
  • Pin 8: Common (COM)

The Modbus connection uses an RJ45 connector.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)




Schneider Electric USA

Attachment(s)
Intergrated Modbus manual.pdf [645.74 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings