What is the correct way to store a Motor Control Center before installation?
Issue:
Storage conditions of Model 6 MCC
Product Line:
Products sold in North America
Resolution:
If the MCC cannot be placed into service upon receipt, store it in a clean, dry, ventilated building free from temperature extremes. Acceptable storage temperatures are from
0 degree C (32 degree F) to 40 degree C (104 degree F). Acceptable humidity levels are 0 to 95%, non-condensing.
If the storage area is cool and/or damp, provide enough heat to prevent condensation inside the MCC.
Note; failure to comply with these recommendations can void the warranty on the product.
Storage conditions of Model 6 MCC
Product Line:
Products sold in North America
Resolution:
If the MCC cannot be placed into service upon receipt, store it in a clean, dry, ventilated building free from temperature extremes. Acceptable storage temperatures are from
0 degree C (32 degree F) to 40 degree C (104 degree F). Acceptable humidity levels are 0 to 95%, non-condensing.
If the storage area is cool and/or damp, provide enough heat to prevent condensation inside the MCC.
Note; failure to comply with these recommendations can void the warranty on the product.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.