What address can you read on the ATV61 and ATV71 drives to show the last fault using Ethernet TCP IP or Modbus?

Issue:
What address can you read on the ATV61 and ATV71 drives to show the last fault using Ethernet TCP IP or Modbus?

Cause:
Wants to read current fault of the drive not the fault history.

Resolution:
LFT or last fault error in address 7121

LFT 0 [No Error] (nOF)
2 [EEPROM Control] (EEF1)
3 [Incorrect Configuration] (CFF)
4 [Invalid Configuration] (CFI)
5 [Modbus Com Interruption] (SLF1)
6 [Internal Link Error] (ILF)
7 [Fieldbus Com Interrupt] (CnF)
8 [External Error] (EPF1)
9 [Overcurrent] (OCF)
10 [Precharge Capacitor] (CrF)
13 [AI2 4-20mA loss] (LFF2)
15 [Input Overheating] (IHF)
16 [Drive Overheating] (OHF)
17 [Motor Overload] (OLF)
18 [DC Bus Overvoltage] (ObF)
19 [Supply Mains Overvoltage] (OSF)
20 [Single output phase loss] (OPF1)
21 [Input phase loss] (PHF)
22 [Supply Mains UnderV] (USF)
23 [Motor short circuit] (SCF1)
24 [Motor Overspeed] (SOF)
25 [Autotuning Error] (tnF)
26 [Internal Error 1] (InF1)
27 [Internal Error 2] (InF2)
28 [Internal Error 3] (InF3)
29 [Internal Error 4] (InF4)
30 [EEPROM Power] (EEF2)
32 [Ground Short Circuit] (SCF3)
33 [Output Phase Loss] (OPF2)
34 [CANopen Com Interrupt] (COF)
37 [Internal Error 7] (InF7)
38 [Fieldbus Error] (EPF2)
40 [Internal Error 8] (InF8)
42 [PC Com Interruption] (SLF2)
45 [HMI Com Interruption] (SLF3)
51 [Internal Error 9] (InF9)
52 [Internal Error 10] (InFA)
53 [Internal Error 11] (InFb)
54 [IGBT Overheating] (tJF)
55 [IGBT Short Circuit] (SCF4)
56 [Motor Short Circuit] (SCF5)
60 [Internal Error 12] (InFC)
64 [Input Contactor] (LCF)
68 [Internal Error 6] (InF6)
69 [Internal Error 14] (InFE)
71 [AI3 4-20mA loss] (LFF3)
72 [AI4 4-20mA loss] (LFF4)
73 [Boards Compatibility] (HCF)
77 [Conf Transfer Error] (CFI2)
79 [AI5 4-20 mA loss] (LFF5)
99 [Channel Switch Error] (CSF)
100 [Process Underload] (ULF)
101 [Process Overload] (OLC)
105 [Angle error] (ASF)
106 [AI1 4-20 mA loss] (LFF1)
107 [Safety Function Error] (SAFF)
110 [AI2 Th Detected Error] (tH2F)
111 [AI2 Thermal Sensor Error] (t2CF)
112 [AI3 Th Detected Error] (tH3F)
113 [AI3 Thermal Sensor Error] (t3CF)
114 [PumpCycle Start Error] (PCPF)
115 [Out Pressure Low] (OPLF)
116 [High Flow Error] (HFPF)
117 [Inlet Pressure Error] (IPPF)
119 [Pump Low Flow Error] (PLFF)
120 [AI4 Th Detected Error] (tH4F)
121 [AI4 Thermal Sensor Error] (t4CF)
122 [AI5 Th Detected Error] (tH5F)
123 [AI5 Thermal Sensor Error] (t5CF)
124 [Anti Jam Error] (JAMF)
125 [Out Pressure High] (OPHF)
126 [Dry Run Error] (DRYF)
127 [PID Feedback Error] (PFMF)
128 [Program Loading Error] (PGLF)
129 [Program Running Error] (PGrF)
142 [Internal Error 16] (InFG)
143 [Internal Error 17] (InFH)
144 [Internal Error 0] (InF0)
146 [Internal Error 13] (InFd)
148 [Motor Stall Error] (StF)
***

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions: Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance: Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings