Video: How to install a shunt or undervoltage trip on an H, J, or L frame breaker
Issue:
How to install a shunt or undervoltage trip on a PowerPacT H, J, or L frame breaker
Product Line:
Molded Case Circuit Breakers
Resolution:
Make sure the breaker is in the tripped position, remove the accossory cover, and install the shunt or undervoltage in the bottom left slot in the breaker (labeled MN/MX). Push the shunt or undervoltage into the slot until it clicks into place. For more information, see attached instruction bulletin or the instructional video below:
How to install a shunt or undervoltage trip on a PowerPacT H, J, or L frame breaker
Product Line:
Molded Case Circuit Breakers
Resolution:
Make sure the breaker is in the tripped position, remove the accossory cover, and install the shunt or undervoltage in the bottom left slot in the breaker (labeled MN/MX). Push the shunt or undervoltage into the slot until it clicks into place. For more information, see attached instruction bulletin or the instructional video below:
Released for: Schneider Electric USA