Can AC current be used to test the Powerpact L frame DC breakers?

Issue:
Testing DC breakers with AC current

Product Line:
Circuit breakers

Resolution:
AC current may be used to test these breakers for thermal tripping at 2xIn or 1.35xIn test per UL-489 SC.
Magnetic trip tests need to be performed using DC current to get accurate results.