Are 100% rated Powerpact B circuit breakers available?
Issue:
Current ratings for Powerpact B
Product Line:
Powerpact B Circuit Breakers
Resolution:
All Powerpact B-frame circuit breakers are 80% rated as standard.
2, 3, and 4 pole unit mounted, 15 A to 60 A breakers may be ordered with UL and CSA certified 100% ratings by adding a "C" suffix to the catalog number.
I-Line breakers and higher ampere breakers are not available with 100% ratings.
Markings on the circuit breaker indicate the minimum enclosure size and ventilation required.
90°C rated wire must be used and sized according to the ampacities of the 75°C wire column in the NEC.
Current ratings for Powerpact B
Product Line:
Powerpact B Circuit Breakers
Resolution:
All Powerpact B-frame circuit breakers are 80% rated as standard.
2, 3, and 4 pole unit mounted, 15 A to 60 A breakers may be ordered with UL and CSA certified 100% ratings by adding a "C" suffix to the catalog number.
I-Line breakers and higher ampere breakers are not available with 100% ratings.
Markings on the circuit breaker indicate the minimum enclosure size and ventilation required.
90°C rated wire must be used and sized according to the ampacities of the 75°C wire column in the NEC.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.