Does Schneider Electric have a list of series ratings for our QED switchboards?

Issue:
What are the series ratings for our QED and CMM switchboards?

Product Line:
Switchboards

Environment:
QED, QED2, CMM

Cause:
Series ratings

Resolution:
There are no series ratings between the main and branches within QED switchboards. They may be able to series rate between the branches with down stream breakers in panels etc.. but not within the switchboard itself.