Do the micrologic 6.0P and 6.0H trip units now come standard with the ERMS label on them?

Issue:
Is the ERMS label on the micrologic 6P and 6H trip units for Masterpact NW, NT, R, and P frame breakers?

Product Line:
Circuit breaker trip units

Environment:
Micrologic 6.0P and 6.0H

Cause:
ERMS switch requiremnt

Resolution:
Yes! As long as next requirements are met, this applyes for old 6P and 6H Micrologic units:

The energy reduction maintenance setting (ERMS) function is available on circuit
breaker equipped with:
• BCM ULP with firmware version 4.0.9 or above.
• MicroLogic P or H trip unit with the blue ERMS label (A) as shown on page 2 from attached Instruction Bulletin.
• IO Module with application switch set to position 3.

Currently, all of the 6.0P and 6.0H trip units come standard with the ERMS label.

https://www.se.com/us/en/download/document/NHA67346/