Overload Compatibility with Everlink Terminal Contactors
Issue:
The overload selected for use with the contactor will not mount or fit correctly. Typically either the contactor or overload has Everlink connections and the other does not.
Product Line:
IEC Contactors and overload relays
Environment:
Tesys D Contactors and LRD/LR3D overload relays
Cause:
Product Compatibility
Resolution:
The LC1D Contactors with Everlink terminations are only suitable for use with the overloads which also have Everlink connectors. These contactors are signified by the letter A in their part number; LC1D40A, LC1D50A, and LC1D65A. The only overloads which can be mounted directly to these units are the LRD313 through LRD365, the LR3D313 through LR3D365, and the LRD313L through LRD365L overloads. Any other overloads will not have the correct Everlink connectors and will not be able to mount directly to these contactors.
The overload selected for use with the contactor will not mount or fit correctly. Typically either the contactor or overload has Everlink connections and the other does not.
Product Line:
IEC Contactors and overload relays
Environment:
Tesys D Contactors and LRD/LR3D overload relays
Cause:
Product Compatibility
Resolution:
The LC1D Contactors with Everlink terminations are only suitable for use with the overloads which also have Everlink connectors. These contactors are signified by the letter A in their part number; LC1D40A, LC1D50A, and LC1D65A. The only overloads which can be mounted directly to these units are the LRD313 through LRD365, the LR3D313 through LR3D365, and the LRD313L through LRD365L overloads. Any other overloads will not have the correct Everlink connectors and will not be able to mount directly to these contactors.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.