ION7550/ION7650 firmware Versions & updates. ION7550/ION7650 Hardware & Firmware Compatibility Matrix.
Issue
Where can I download ION7550/ION7650 firmware and what was updated between firmware versions? What hardware and firmware versions are compatible with each other?
Product Line
ION7550/ION7650
Environment
Firmware Download Links
Resolution
*Warning: The firmware utilities listed here can cause permanent damage to your product if applied incorrectly. Before downloading any firmware updates, verify the firmware you are downloading is appropriate for the specific model number of your product. If you have any doubts, contact Technical Support for guidance.*
*Warning: Devices should be disconnected from all monitoring software before performing a firmware upgrade*
The table below lists the current and past firmware versions with associated downloads and What's New? document links:
Note: determine the hardware version of the meter from meter serial number, e.g. if the meter serial number is MW-1109A055-01, then its hardware version is -01, in this meter example firmware could be updated til v375.
| Firmware Version | ION7650 Firmware* | ION7550 Firmware* | What's New? Document | Notes | Release Date |
| V416 | Download | Download | Details | Only compatible with -05 hardware | May 2019 |
| V411 | Download | Download | See Below | Only compatible with -05 hardware | July 2018 |
| V410 | Download | Download | Details | Only compatible with -05 hardware | March 2017 |
| V401 | Download | Not Available | Details | Only compatible with -05 hardware | March 2016 |
| V400 | Download | Not Available | Details | Only compatible with -05 hardware | Feb 2015 |
| V375 | Download | Download | See Below | Use for -04 and older hardware | July 2018 |
| V374 | Download | Not Available | Details | March 2016 | |
| V373 | Download | Download | Details | Dec 2014 | |
| V371 | Download | Download | See Below | June 2012 | |
| V366 | Download | Download | See Below | Feb 2012 | |
| V360 | Not Available | Download | Details | ||
| V355 | Not Available | Not Available | Details | ||
| V350 | Not Available | Not Available | Details | ||
| V331 | Not Available | Not Available | See Below | ||
| V330 | Not Available | Not Available | Details | ||
| V321 | Not Available | Not Available | Details |
* Older versions with 'Not Available' status may be requested from Technical Support if required.
** RTU stands for Remote Terminal Unit
Additional descriptions for firmware versions are as follows:
V416
V411/375
V410
V400
V400 is a general firmware release that adds support for new metering hardware. In addition this firmware release reduces the 7x50e and 7x50s variants into one allowing for IEC61850 and10Meg of logging memory to occur upon the same device. V400 adds compatibility for the -05 hardware revision option. This can be found as the last two digits of a meters serial number. V400 will NOT be compatible with previous versions of hardware ( -04 or earlier). In addition previous firmware revisions (pre V400) will not be compatible with the -05 hardware. We have consolidated the e (IEC61850) and s (standard) variants into one release. This means ALL devices ordered with V400 will now contain IEC61850 functionality as well as contain the 10M logging memory. Both features can be implemented in frameworks simultaneously. NOTE: To support the new features in v400, download the latest version of ION Setup from the website.
V401/374
*The V374s version is the standard version. *The V374e version is for IEC61850 protocol support. This firmware is for the older hardware platform (RevA, if you like). The equivalent firmware for the RevB hardware platform is V401.
V373
Important Notes: *Generally, two versions of firmware are available for the ION7x50 devices: V---e with IEC 61850 implementation, and; V---s without IEC 61850 implementation. *IEC61850 is supported with the consequence of a reduction of the available logging memory. If you upgrade a 10MB meter to use IEC 61850 firmware, the meter’s logging memory will be reduced to 5MB. If the meter is subsequently loaded with non-IEC 61850 firmware, the meter’s original logging memory will be restored.
V371
Firmware V371 is a general firmware release that adds support for the initial release of the PowerLogic Remote Display and also includes security enhancements. In preparation for upgrading your meter's firmware please download the latest firmware version (.upg file) and the appropriate Meter Template (.dcf file). ION Setup (freeware utility) is the recommended tool for the firmware upgrade process. See the Upgrading ION Device Firmware technical note for complete details.
Important Notes: *Two versions of firmware are available below namely: V371e with IEC 61850 implementation, and;V371s without IEC 61850 implementation. *IEC61850 is supported with the consequence of a reduction of the available logging memory. If you upgrade a 10MB meter to use IEC 61850 firmware (7650V360e), the meter’s logging memory will be reduced to 5MB. If the meter is subsequently loaded with non-IEC 61850 firmware (7650V360s), the meter’s original logging memory will be restored.
V366
Firmware version 366 (V366) for the ION7x50 adds Modbus mastering over TCP support for up to 10 connections. This is in addition to the 8 available Ethernet connections and is also in addition to the Modbus master functionality in both serial ports. This release also includes various communications bug fixes. When upgrading your meter's firmware please download the latest firmware version (.upg file) and the equivalent Meter Template (.dcf file). You can upgrade meter firmware using ION Setup or ION Enterprise. See the Upgrading ION Device Firmware technical note for complete details
Important Notes from V360 (applicable to V366): * Two versions of V360 firmware are available below: with IEC 61850 implementation (7x50V360e) and without IEC 61850 implementation (7x50V360s). * IEC 61850 can only be purchased on 5MB meters, not 10MB meters. If you upgrade a 10MB meter to use IEC 61850 firmware (7x50V360e), the meter’s logging memory will be reduced to 5MB. If the meter is subsequently loaded with non-IEC 61850 firmware (7x50V360s), the meter’s original logging memory will be restored.* The non IEC 61850 firmware version (7x50V360s) still has new features available, such as COMTRADE waveform recording.* To find ICD files related to the IEC61850 implementation on ION7x50 meters, search the keyword icd on any schneider-electric.--- site
V360
Firmware version 360 (v360) for the ION7550/ION7650 adds IEC 61850 server functionality. This includes FTP support and the ability to save waveform data in COMTRADE format.
V355
Firmware version 355 (v355) and factory template 7550/7650_v355_FACPQ_V3.4.0.0.0 for the ION7550 / ION7650 adds International Electrotechnical Commission (IEC) 61000-4-30 Class A Edition 2 standard compliance for the ION7550 / ION7650 and the ability to configure the event priority value for digital input state change events.
V350
Firmware version 350 (v350) for the ION7550 / ION7650 adds a number of new features as well as support for the new Communications Card.
New features
- Disturbance Direction Detection capabilities are now available.
- Localization options have been added to the meter, including:
- the ability to set the language of the front panel display to English, Spanish, French or Russian.
- the option to customized IEEE/IEC convention settings.
- Setpoint learning functionality has been added.
- The meter can function as a Modbus gateway, forwarding Modbus packets from a master through the meter to downstream serial devices.
- Trending and Forecasting functionality has been added.
- The meter can now communicate selected values over the Ethernet via SNMP.
- Support for a new communications card has been added.
- A default IP Address has been added. For more information on these features, see the relevant sections in this document.
Other changes
- Power Availability has been removed from the default template.
- V4, I4, I5 waveform recorders have been removed from the default template.
- Thermal Demand has been removed from the default template.
V331
Firmware version 331 (v331) for the ION7550/ION7650 meter improves Class A compliance with the IEC 61000-4-30 (2003 - 1st Edition), or “4-30” power quality standard. Compliance improvements included are Class A Flicker with no exceptions
V330
Firmware version 330 (v330) for the ION7550 / ION7650 meter supports Class A compliance with the IEC 61000‐4‐30 (2003 ‐ 1st Edition), or “4‐30” power quality standard.
V321
Firmware version 321 features enhanced Modbus Mastering with four ION modules new to the ION 7550 /ION 7650 platform. The Modbus Master Device and Modbus Master Mapping modules work together to offer improved setup of Modbus read functionality. The Averaging module provides simple averaging and easily links with other Modbus modules. The Modbus Master Options module allows multiple serial connections to different loops of Modbus devices.
Advanced meter security provides an additional layer of security, allowing you to configure up to 16 users, each with unique access rights to the meter. Access rights consist of different security levels, permitting different users to read values, perform resets, time sync the meter clock, or configure meter settings.
Released for: Schneider Electric USA
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.