What are the coil characteristics of the LXD3G7, LXD3LE7, LXD3W7, and LXD3T7 coils?

Issue:
Identify the coil characteristics of the LXD3G7, LXD3LE7, LXD3W7, and LXD3T7 coils

Product Line:
IEC Contactors - GIC Product

Environment:
US Product

Cause:
Product Specification

Resolution:
The LXD3G7, LXD3LE7, LXD3W7, and LXD3T7 are coils designed specifically for the US market and are different in characteristics from the other LXD3 coils available:
LXD3G7 - 120V 60hz only with a tolerance of -15% and +10%.  Inrush 200VA and holding 19VA
LXD3LE7 - 208V 60hz only with a tolerance of -15% and +10%.  Inrush 200VA and holding 19VA
LXD3W7 - 277V 60hz only with a tolerance of -15% and +10%.  Inrush 200VA and holding 19VA
LXD3T7 - 480V 60hz only with a tolerance of -15% and +10%.  Inrush 200VA and holding 19VA