How can you copy an ATS22/ATS48 program from one soft starter into another one?

Issue:
Is it possible to transfer the settings from an old ATS22/ATS48  soft starter to a new or replacement identical softstart?

Resolution:
If you have a laptop available, you can copy the settings from an old ATS22/ATS48 assuming it is still in working condition using the SoMove software to download the settings to your PC then uploading them back to your new ATS22/ATS48

You will need to download SoMove (Free)
https://www.schneider-electric.ca/en/download/document/SoMove_FDT/

The required libraries for the ATS22/ATS48
https://www.schneider-electric.us/en/download/document/Altistart_DTM_Library/

You will need to buy or use the Modbus cable TCSMCNAM3M002P

After successfully connecting the existing ATS22/ATS48

  • Save the project as a PSX file on your computer.
  • Now Connect to the new ATS22/ATS48 to SoMove
  • Open the project you saved earlier and upload it to the new ATS22 or ATS48 softstart.


If you are having issues connecting to your ATS22/ATS48 check the link below for troubleshooting
https://www.schneider-electric.ca/en/faqs/FA313062/


Note: Both the old and the new soft starters have to be identical otherwise you can not copy the settings from one another without some modifications of some parameters or manually making the changes.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalogue
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings