{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Schneider Electric USA Website

Welcome to our website.
How can we help you today?
What is the permissible current depending on the ambient temperature on the connections of a Compact NSX NA switch disconnector installed in Prisma P enclosure?
The maximum permissible current on the connections of a Compact NSX NA switch disconnector is influenced by the ambient temperature around the switchboard. The derating for the switch disconnectors that has to be applied is equal to the values published in the attached table corresponding to the NSX circuit breaker with electronic trip units.

Schneider Electric USA

Attachment(s)
Designing connections.pdf [174.08 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: