What Is the Difference Between IL1R (Logic Input Real Image) and IL1I (Logic Input Physical Image) on Altivar Process Drives?

Resolution:
IL1I and IL1R represent two different states of the drive's logic inputs:

  • IL1I (Logic Input Physical Image): Represents the actual physical state of the logic input terminals.
  • IL1R (Logic Input Real Image): Represents the logic input state used internally by the drive after any configured logic inversion has been applied.

For example, if DI2 is physically high, its physical image in IL1I is 1. If DI2 is configured with inverted logic, the corresponding real image in IL1R becomes 0.

A simple way to understand the relationship is:

Physical input → IL1I → Logic processing/inversion → IL1R → Drive function

If no logic inversion is applied, the physical and real images are the same:

IL1R = IL1I

The two values may differ when the drive needs to invert the state of a logic input before using it for an assigned function.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings