How do you properly connect or wire a transformer with the voltage code T2F?

Issue:
How is a transformer with the voltage code T2F wired or connected?

Product Line:
Transformer

Environment:
T2F transformers

Resolution:
For 480v delta to 208/120V 3 phase 4 wire.
Connect 480v to H1, H2, H3, and cap off all other H wires individually.
For 208/120V  connect X1, X2, X3 to the load and X0 to the neutral. See wiring diagram below.
wire wire1