How Does Basic Wiring on ATV600 or ATV900 Compare to ATV61 or ATV71?

Article available in these languages:

  • Spanish

Resolution:

The basic wiring of ATV600 / ATV900 Process Drives is largely similar to that of ATV61 / ATV71 drives, with some key differences outlined below:

Digital Inputs (DIs):
Digital Inputs on ATV61/ATV71(labeled LI – Logic Inputs) function the same as the, Digital Inputs on ATV600/ATV900 (labeled DI - Digital inputs).

Analog Inputs (AI):
AI1 and AI2 are wired the same as on ATV61/ATV71.
However, ATV600/ATV900 do not support a bipolar input on AI1, which was available on ATV61/ATV71.

Analog Outputs (AO):
AO1 on ATV61/ATV71 corresponds to AQ1 on ATV600/ATV900.

Digital Outputs (DO):
ATV600/ATV900 use DQ+ and DQ‑ terminals for Digital Outputs.

Relay Outputs:
R1, R2, and R3 are programmable relays and provide functionality similar to the relays on ATV61/ATV71.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric USA

Explore more
Category:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Category:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings