How can we help you today?

what are the electrical characteristics of voltage inputs of DM6000H meter ?

Voltage inputs

VT primary: 100 V L-L to 999 kV L-L maximum, starting voltage depends on the VT ratio
V nominal:   Up to 277 V L-N / 480 V L-L (selectable VT secondary from 100, 110, 115, 120 to 415 V L-L)
Measured voltage with full range:  35 to 600 V AC L-L
Permanent overload (withstand):  750 V L-L, continuous
Operating voltage range with accuracy:  80-480 V L-L ± 10%, Category III
Impedance:  ≥ 5 MΩ
Frequency:   50 / 60 Hz nominal ± 2 Hz
VA burden:   ≤ 0.2 VA at 240 V AC L-N at 50Hz

Schneider Electric USA

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings