How can we help you today?

Video: How to reset the surge counter on the front display of the Surgeloc SPD.

Issue:
Clearing the surge counter on SurgeLogic Surgeloc SPD.

Product Line:
Surgeloc Surge Protective Devices (SPDs)

Environment:
NQ internally mounted assembly

Cause:
It may be desired to reset surge counter after changes are made to surrounding electrical environment.

Resolution:
The surge counter displays the number of transient voltage surges since the counter was last reset. To reset the surge counter press and hold the “Test” button for approximately 6 seconds.

Schneider Electric USA

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Tech Support: 877-342-5173
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Software and Firmware
  • Product Selector
  • Product Replacement
  • DigestPLUS Online Catalog
  • Industries
  • Partners
  • Schneider Electric Community
  • Events
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings